Sale!

150 KVA Sub-Station

Original price was: 3,287,630.00৳ .Current price is: 2,843,530.00৳ .

Supply of powder coated (16-18SWG) sheet steel clad, dust and vermin proof, free-standing,
floor mounting type completely factory assembled 3-phase, 4-wire 415V, 50 Hz indoor type
Low Tension (LT) switchgear panel having 1000A hard drawn electrolytic copper bus bars &
comprising of followings:
Incoming:
1 – 250A, 36KA, TP, MCCB, adjustable thermal overload & magnetic short circuit release.
Model: CVS
3 – Current transformer having ratio 250/5A with suitable accuracy & burden.
3 – Phase indicating lamps.
1- No Multi-Functional Meter
Outgoing:
01 x 160A, 25 kA, TP MCCB adjustable thermal overload & magnetic short circuit release
(For PFI)
01 x 63A, 25 kA, TP MCCB adjustable Type thermal overload & magnetic short circuit
Release. (For Lift)
10 x 40A, 25 kA, TP MCCB adjustable thermal overload & magnetic short circuit release
01 x 32A, 10 kA, TP MCB adjustable Type thermal overload & magnetic short circuit
Release
05 x 32A, 10 kA, SP MCB adjustable Type thermal overload & magnetic short circuit
release
Origin: India
Circuit Breaker: Schneider Electric, / Equivalent
Meter: Selec, India
Internal wire: BRB/RR/equivalent Bangladesh.
Assembled By: EMS PowerTech Ltd.

Description

Technical specification of 150KVA, 11/0.415 KV, 3- Transformer:
SL No Descriptions
01
3 phase oil immersed, naturally air-cooled transformers acc. To VDE/IEC/DIN/BSS and IEC-76
Standard with 3 HT Bushing and 4 LT Busing arranged on tank top, Oil level indicator, drain
and filling valves, lifting lugs with first filling of oil in transformer
Rated Capacity: 150KVA
Rated Frequency: 50 Hz
Rated voltage –
Primary: 11000V
Secondary: 415/240V
Vector Group: Dyn 11
Rated primary current: 7.87A
Rated secondary current: 209.8A
Type of cooling: ONAN
Type of loading: Distribution
Tap changer: Off load manual type.
No of tap positioning: -7.5%, -5 %, -2.5%, 0, + 2.5%, of rated KV.
Ambient temperature: 40° C
Insulation Class: A
Temperature risein oil: 60° C (Max)
-Coil: 65° C (Max)
Neutral brought Out & loaded up to: 100 %
Max service altitude: 1000 Meters
Installation: Indoor/ Outdoor
No load loss: 480 Watt
Load loss: 2800 W +10%
Impedance: 4.0 % (Approx)
Efficiency at full load (Economy load): 99.56 %

Accessories:
1) Silica gel breather.
2) Dial type thermometer.
3) Horn gap arrester.
4) Conservator.
5) Lifting lugs.
6) Earthling terminals.
7) Name -plate.
Origin:
Core: Nippon, Japan/Kawasaki, USA
Insulating materials: Wiedemann, Switzerland
Copper: BRB Cables, Bangladesh
Transformer Oil: Savita, India
Manufactured by: Trade Engineering/Addex/Bachar/Equivalent.

Reviews

There are no reviews yet.

Be the first to review “150 KVA Sub-Station”

Your email address will not be published. Required fields are marked *

Time limit exceeded. Please complete the captcha once again.